Module 3. Transformers

Lesson 12

 VECTOR DIAGRAM AND LOSSES

12.1  Vector Diagram without Load 

Let us consider a transformer without load (Fig. 12.1). Primary winding of the transformer is supplied with sinusoidal alternating voltage V1 and current Im flows through it. This current Im lags behind the applied voltage V1 by 90o as primary coils exhibit pure inductance. Magnetic flux produced in the core is in phase with Im. Emfs E1 and E2 are induced in the primary and secondary winding of the transformer respectively. Phasor diagram of E1 and E2 are shown in Fig. 12.2 and 12.3. When transformer is on no load, a small current I0 (2-10% of Im) known as exciting current is taken up by the primary winding. This current I0 lags behind the voltage vector V1 by an angle o.

Fig. 12.1 Transformer under no load condition

phase 1.jpg

Fig. 12.2 Phasor diagram for the primary side of transformer

phase 2.jpg

12.3 Phasor diagram for the secondary side of transformer

12.2  Vector Diagram with Load 

 Consider a transformer with load (Fig. 12.4).  I2 current flows through the secondary winding and magnitude of I2 depends on the terminal V2 voltage and impedance of the load. The phase angle of secondary current I2 depends upon the nature of load i.e. whether the load is resistive, inductive or capacitive. I0 is the no load current. The secondary current I2 is in phase, lags behind and leads the secondary terminal voltage for resistive, inductive and capacitive load respectively.

transformer 3.jpg

 

Fig. 12.4 Transformer with load

 

phasor 3.jpg

Fig. 12.5. Phasor diagram for the primary side of transformer

phasor 5.jpg

Fig. 12.6 Phasor diagram for the secondary side of transformer

 

12.3  Losses in Transformer

There are certain losses in a transformer which are as follows:

12.3.1  Iron losses

Iron core of the transformer is subjected to alternating flux which causes eddy current and hysteresis loss in it. The sum of these two losses is known as iron or core loss. The iron losses depend upon the construction material of core, frequency of a.c. supply, maximum flux density in the core, volume of the core etc. The value of iron looses is very small compared to copper loss.

a  Eddy current loss

Due to the alternating magnetic flux current is induced in the core of the transformer which is known as eddy current. If transformer core was made of solid material (Fig. 12.7) the magnitude of eddy current and thus losses would be very high. Therefore core of the transformer is made of laminated sheets (Fig.12.8).

Eddy current loss

Where A is constant 

 

Fig. 12.7 Solid transformer core (high eddy current loss)

Fig. 12.8 Laminated transformer core (low eddy current loss)

b.  Hysteresis losses

When the steel core of the transformer is magnetized and demagnetized by the alternating flux heat is generated. This causes hysteresis losses. 

Hysteresis loss

 

 

 Where A and B are constants

12.3.2  Copper loss due to winding resistances

The primary and secondary windings are made of copper wires which has certain resistance. If resistance of primary and secondary windings are R1 and R2 respectively, Copper loss will be given as:

Total copper loss = I12R1 + I22R2

Where,

I1 and I2 are current flowing through primary and secondary winding respectively.

12.3.3  Leakage flux losses

Magnetic flux is produced in both the windings of the transformer (primary and secondary). The flux which links both the winding is the useful flux and is called mutual flux. The fluxes which do not link with the other winding are known as leakage flux.

12.3.4  Stray losses

Losses caused due to eddy current in channels, bolts etc.

12.4  Transformer Test

The performance of a transformer can be determined by:

1. Open-circuit or no-load test.

2. Short-circuit or impedance test.

12.4.1  Open-circuit or no-load test

Open-circuit or no-load test is done to determine:

     i.   No-load loss or core loss.

   ii.   No-load current I0 by which equivalent resistance R0 and leakage resistance X0 can be calculated

For no load test, one of the transformer winding is kept open and the other is connected to voltage source at rated frequency (Fig. 12.9). No-load current (I0) is measured using ammeter. No-load power (P0) is measured by wattmeter.

Fig. 12.9 Diagram for open-circuit test

Primary no-load current I0 in Low Voltage (LV) winding is very small 2 to 10% of rated load current due to which the copper loss (Io2R1) is negligibly.  As the secondary side is open, no current flows in secondary so copper loss or winding loss is zero. Thus the power measured by wattmeter is due to core loss.

No load input power = P0 = V1 I0 cosϕ0        

Where,

P0 = No load input power = Core loss or iron loss

cosϕ0 =no-load power factor =  = P0/V1I0

I0 = no-load current

V1 = primary voltage

 No-load current I0 has two components and is given as:

 

a. No-load current wattful component (iron loss component),

b. No-load current magnetizing component (produces magnetic flux in core),

No-load resistance is given by

No-load reactance is given by,

 No-load current I0 drawn by the transformer is the exciting current. Admittance Y0 of the transformer is given by:

The exciting core loss conductance ,

The exciting or magnetising susceptance ,

12.4.2  Short-circuit or impedance test

This test is done to measure:

(i) Full-load loss or copper loss (in the winding)

(ii) Equivalent resistance and reactance referred to measuring side.

In this test, the secondary (low-voltage winding) is short-circuited by a thick wire (Fig. 12.10) and low voltage i.e. 5 to 10% of rated primary voltage is applied to the primary winding.

Fig. 12.10 Diagram of short-circuit test

The low input voltage is gradually raised till at voltage VSC, full-load current I1 flows in the primary. As the input voltage is small the magnetic flux linking the primary and secondary side is very small. Thus iron losses can be neglected. The wattmeter only measures the copper loss. Fig. 12.11 shows the equivalent circuit of a transformer on short circuit as referred to primary side. As no-load current I0 is small it is neglected in the equivalent circuit.

 

Fig. 12.11a Equivalent circuit of transformer under short circuit condition.

Fig. 12.11b Equivalent circuit of transformer under short circuit condition.

 

Full load copper loss = W (wattmeter reading)

VSC= Applied voltage applied so that  full-load current I1 flows in the primary winding

I1 = reading of the ammeter on the primary side

Total impedance as referred to primary side

 

Total resistance as referred to primary side

 

Total reactance as referred to primary side