Site pages
Current course
Participants
General
20 February - 26 February
27 February - 5 March
6 March - 12 March
13 March - 19 March
20 March - 26 March
27 March - 2 April
3 April - 9 April
10 April - 16 April
17 April - 23 April
24 April - 30 April
Lesson 18. Dual compression and individual compressors systems, compound compression
Module 5. Multi-evaporator and compressor systems
Lesson 18
DUAL COMPRESSION AND INDIVIDUAL COMPRESSORS SYSTEM, COMPOUND COMPRESSION
18.1 Introduction
It is a compressor having a low pressure inlet valve, medium pressure inlet ports and high pressure discharge valve. Thus, the purpose of such compressor is to take vapour from two different evaporators which are at different pressures. The discharge of the compressed refrigerant is at some common discharge pressure. The dual compressor is used to replace two compressors which are required for two sources of refrigerant vapour. A simple form of the dual compressor is shown in Fig. 18.1. The compressor consists of low pressure suction valve, medium pressure suction ports and high pressure delivery valve.
Fig. 18.1 Multi-evaporator and expansion with individual compressor system
Fig. 18.2 showing the expansion of liquid refrigerant from P3 to P2 (3-4) and vapour produced in the expansion process is directly passed to dual compressor. The corresponding P-H diagram is shown in Fig. 18.3.
Fig. 18.2 Dual compressor with multi-expansion valve
Fig. 18.3 P-H diagram of dual compressor with multi-expansion valve
A dual compressor with multi loads at different temperatures is shown in Fig. 18.4. Evaporators are provided with individual expansion valves. Dual compressor pumps the vapour from E1 and E2 evaporators and delivers to a condensing pressure. The corresponding P-H diagram is shown in Fig. 18.5. The analysis of such system can be done by calculating the mass flow rate in E1 and E2 based on the capacity of these evaporators. The vapour is compressed from point hm to h2 and rise in enthalpy during compression gives the work of compression.
Fig. 18.4 Dual compressor with multi-loads
Fig. 18.5 P-H diagram of dual compressor with multi-loads
18.2 Individual Compressor System
Dual compressor pumps vapour refrigerant from two separate evaporators without affecting the performance of the system while individual compressor requires two compressors. A vapour compression refrigeration system consisting of multi-evaporators with multiple expansion valves having individual compressor is shown in Fig. 18.6.
Fig. 18.6 Multi-evaporator and expansion with individual compressor system
Fig. 18.7 P-H diagram of Multi-evaporator and expansion with individual compressor system
The corresponding P-H diagram is shown in Fig. 18.7. Assuming, T1 and T2 are the refrigeration load on E1 and E2.
Power required for C1 = m1 (h3-h2) kW
Mass of refrigerant handled by C2 compressor is given as under.
mC2 = m1 + m2 + mv
Where, mv = mass of refrigerant vapour carried with (m1 + m2)
Power required for C2 = mC2 (h4 – h8) kW
Total power required for the system = (C1 + C2) kW
COP of the system= (3.5 (T1+T2))/(m1 (h3-h2 )+mC2 (h4-h8 ) )